Grounding and bonding are electrical subjects, and the electrical engineer of record owns them. But walk through a data hall and count what actually gets bonded: cabinets, open racks, ladder racks, cable tray, busway supports, containment frames, the steel that carries all of it, and often the building columns themselves. Most of it is steel, and most of that steel is coated. Data center grounding and bonding therefore lands on the structural package in a very practical way: where the bond points are, whether the metal is bare there, and how the coating is handled. This article reads the guidance in the Data Center Handbook edited by Hwaiyu Geng (2nd edition, Wiley, 2021) from that angle.
Code grounding and data center grounding are not the same
Chapter 16 of the handbook reminds readers that the US National Electrical Code (NEC Article 645.15) requires all exposed non-current-carrying metal parts of an IT system to be grounded, which includes the metal rack and everything mounted in it. That is the floor.
Chapter 23 goes further. It explains that the recommended methods for grounding racks and cabinets exceed the minimum requirements of building codes. Code grounding exists for life safety. Standards such as ANSI/BICSI 002 Data Center Design and Implementation Best Practices and IEEE 1100 Recommended Practice for Powering and Grounding Electronic Equipment add guidance for safety, noise control and the protection of sensitive electronic equipment. The telecommunications bonding standard named in the handbook's survey of cabling standards (Chapter 12) is ANSI/TIA-607, with ISO/IEC 30129 and CENELEC EN 50310 as its international counterparts.
For the steel designer, the difference matters because a life-safety ground can tolerate a mediocre joint that a noise-control bond cannot.
Bare metal at every bond
The handbook is specific. Racks and cabinets should be provided with a bonding point for connection to the data center grounding system, and that bonding point should provide metal-to-metal contact without any paint or powder coating inhibiting the effectiveness of the bond. It adds that the resistance to true earth should be 5, 3 or 1 ohm, measured by the fall of potential method (IEEE Std 81), depending on the data center class under BICSI 002.
Chapter 16 makes the same point at the scale of a single rack: where a grounding wire is attached, the paint should be scraped off to ensure conduction, and special grounding screws with teeth under the head are used to bite through to bare metal.
Racks come from the IT vendor, but the same rule applies to every piece of steel the grounding design asks to bond: overhead support frames, ladder rack supports, busway hangers, containment structures and, where the electrical design uses them, building columns and the roof frame. If that steel arrives fully painted, someone on site must grind the coating away at each bond, then protect the cut edge. On a large hall that is hundreds of points, done at height, after the fact.
When there is no raised floor
Many new data halls are built slab on grade with all services overhead. Chapter 23 points out one consequence that is easy to miss: without a raised floor, the underfloor supplemental bonding grid that IT equipment traditionally relied on is no longer available, so a proper overhead grounding system has to be provided instead.
That pushes the bonding network into the same space as the busway, cable trays and containment, all of which hang from steel. The supplemental bonding conductors now run along or beside the overhead support steel, and they need somewhere to land. The support frame becomes part of the bonding route, not only a hanger.
The same chapter notes that the entrance room should sit close to the electrical room where the main building ground bus bar is located, to keep the telecommunications bonding conductor short. Short, direct bonding paths are a recurring theme, and they are easier to achieve when the steel layout and the grounding layout are drawn together.
What the steel package can do
Most of the friction around grounding comes from coatings, and coatings are decided in the shop. Planning bond points before fabrication avoids field grinding:
| Item | Shop approach |
|---|---|
| Bond pads | Small bare or galvanized pads welded to support frames at the positions the electrical drawings show |
| Bond holes | Drilled or laser-cut holes sized for the grounding lug, so no field drilling through coated steel is needed |
| Coating masking | Masking of the contact area during painting, with the masked area shown on the shop drawing |
| Galvanized members | Hot-dip galvanized supports that keep a metallic, conductive surface, still cleaned at the lug |
| Splice continuity | Bolted splices in overhead frames noted where the bonding design needs electrical continuity across the joint |
| Touch-up | Specified touch-up around any bond made through paint, so the cut edge does not start corrosion |
Hot-dip galvanizing deserves a note. A zinc coating is metallic and conductive, so a galvanized support is far friendlier to bonding than a painted one, although contact surfaces should still be clean. Our hot-dip galvanizing page explains the process, and the article on paint, galvanizing or duplex coating covers the trade-offs.
Coordination on the drawings
The practical rule is simple: if the electrical design names a steel element as a bonding point, that point should appear on the steel shop drawings. Good coordination usually covers:
- A bonding schedule from the electrical engineer listing which steel elements are bonded and where;
- Bond pad and hole details placed on the support steel drawings, with the masking extent;
- Column bonding positions if the grounding design bonds building steel, typically near column bases or at each grid line;
- Overhead frame continuity, so the bonding conductor route along the support steel is unbroken;
- Inspection, so masked areas and pads are checked before shipment, like any other shop item.
Overhead support steel for busway and trays is covered in our cable support steel and cable tray supports pages, and the frames that carry it in the data hall frames guide.
Corrosion and the bond
A bond made by grinding through paint leaves bare steel at the edge of the lug. In a dry, conditioned data hall that is a small risk, but in outdoor equipment yards, at louvers, in economizer plenums or in coastal climates it is a real one. The handbook's discussion of humidity and contamination is a reminder that data halls are not always as benign as they look. Specifying the bonding approach and the touch-up together keeps the bond conductive and the steel protected.
Questions for the brief
Before steel is detailed, it helps to ask:
- Which BICSI 002 class is the facility, and what resistance to earth does the electrical design target?
- Is there a raised floor, or does the bonding network run overhead on the support steel?
- Which steel elements are bonded: racks only, overhead supports, columns, roof frame?
- Are supports painted, galvanized or duplex, and how is each bond point prepared?
- Who touches up bonds made in the field, and to what specification?
Where World Steel fits
World Steel designs and fabricates the structural frame and the overhead support steel for data halls, and adds bond pads, lug holes and coating masking to the shop drawings at the positions the electrical engineer specifies. Fabrication, painting and galvanizing are done in our own plant in Vietnam with inspection accredited under IAS AC472, so masked areas are checked like any other shop item before the steel ships to the US port. Our customers are US contractors; site work, including erection and the grounding installation, is their scope, and their Engineer of Record approves and seals the design. See the data center building package for the full shell scope.
Key takeaways
- Data center grounding goes beyond code: BICSI 002 and IEEE 1100 add noise control and equipment protection to life safety.
- The handbook asks for bonding points with bare metal-to-metal contact, and 5, 3 or 1 ohm to true earth depending on class.
- Without a raised floor, the supplemental bonding grid moves overhead, onto the same steel that carries busway and trays.
- Bond pads, holes and masking planned in the shop avoid field grinding through coatings and the corrosion that follows.
Source: H. Geng (ed.), Data Center Handbook, 2nd ed., Wiley, 2021, Chapters 12, 16 and 23; ANSI/TIA-607; ANSI/BICSI 002; IEEE 1100. Ideas are paraphrased; consult your Engineer of Record for project decisions.
Quick answers
Why does a data center need more than code grounding?
Building codes set grounding for life safety. Data center standards such as ANSI/BICSI 002 and IEEE 1100 add requirements for noise control and protection of sensitive electronics, so the recommended methods go beyond the code minimum.
What resistance to earth is recommended?
The Data Center Handbook notes that the resistance to true earth should be 5, 3 or 1 ohm, measured by the fall of potential method, depending on the BICSI 002 class of the data center.
Why does paint matter for grounding?
A bond needs metal-to-metal contact. Paint or powder coating at the bonding point weakens the bond, so the coating must be left off or removed there, or toothed hardware used that cuts through to bare metal.
Who designs the grounding system?
The electrical engineer of record designs the grounding and bonding system. The steel supplier provides the bare bond pads, holes and coating masking that the electrical design calls for, shown on the shop drawings.
Keep building your steel plan
Go further on USPEB.com
On this topic
Across the US market
- US codes and standardsIBC, AISC, AWS and MBMA, designed to
- Seismic steel structuresSDC D to F framing for West Coast jobs
- Crane building designUS crane standards for mill and bay buildings
- Design ReportWhat our US-code design report contains
- Large projects, 2,500 t a monthCapacity for large US general contractors
- Contractor partnershipLong-term supply for US contractors