Chapter 28 of the Data Center Handbook edited by Hwaiyu Geng (2nd edition, Wiley, 2021), written by fire protection engineers from Jensen Hughes, sets out the goals of data center fire protection in three lines: protect people, give users and responders accurate information, and limit loss of life, downtime, equipment and data. For a data center, the third goal drives most decisions, and it is where NFPA 75, insurer standards and tier requirements come in. This article summarizes the handbook's guidance on suppression and detection and explains how those choices affect the building and its steel.
Codes, standards and who decides
The handbook separates three layers of fire requirements.
Model codes. In the US, the International Building Code and International Fire Code, or NFPA 101 where adopted, set minimums for type of construction, occupancy, egress, suppression, detection and hazards such as batteries and generator fuel. Data centers have historically been classified as business occupancies. The handbook notes that as they become larger and more autonomous, a storage classification is conceivable, though business remains more common.
NFPA 75. The Standard for the Fire Protection of Information Technology Equipment covers active and passive protection and risk analysis. The handbook points out that it is not referenced by the IBC or NFPA 101, and is referenced by the National Electrical Code only as a non-required standard. It is therefore enforceable only where adopted. Among other provisions, it requires fire separation of IT rooms, sprinkler protection if the building requires sprinklers, and automatic detection.
Owner and insurer standards. Insurers such as FM Global publish data sheets for electronic data processing and clean agent systems that can exceed the codes. Tier standards add more: the handbook notes that Tier I and II facilities typically meet code minimums, while Tier III and IV facilities may require both sprinkler and clean agent suppression.
The design team must know which layers apply before the building is designed, because several of them change the structure.
Why fire is different in a data center
The handbook lists the fuel in a computer room: circuit boards, wiring insulation, plastic in cabinets, furnishings, backboards, batteries and floor tiles. Rising rack density brings more heat and a higher risk of overheating if cooling falls behind. It recommends good housekeeping and, where possible, putting batteries and nonessential equipment in separate rooms.
It also explains why early detection matters so much. Burning electronics release corrosive gases such as hydrogen cyanide and hydrogen chloride, which can damage printed circuit boards more than the heat itself. Electrical insulation can smolder for a long time before flaming. Catching a fire at the incipient stage lets staff respond before an emergency develops.
Suppression choices
The handbook reviews the main options:
| System | Notes from the handbook |
|---|---|
| Sprinklers, often preaction | The baseline where codes require sprinklers; preaction systems keep pipes dry until detection and sprinkler operation |
| Clean agent | Preferred where water would cause irreversible damage; some agents can break down under heat, so quick knockdown and evacuation matter |
| Water mist | Smaller droplets, higher pressure; must be fire tested for the actual application, so a system approved for machinery spaces is not approved for a data center |
| Hybrid water and inert gas | Newer technology, with an NFPA standard in development at the time of writing |
| Hypoxic air | Not a viable option for occupied spaces in the US |
| In-cabinet systems | Clean agent or CO2 within the cabinet, as a supplement |
Where suppression meets the structure
Fire protection choices have structural consequences that are easy to miss until coordination.
- Sprinkler clearance and clear height. TIA guidance summarized in Chapter 12 calls for at least 460 mm (18 in) between cabinet tops and sprinklers. Together with tray stacks, busway and containment, that clearance sets the clear height under the roof steel.
- Hung loads. Sprinkler mains, preaction valves and branch lines, often doubled where both sprinklers and clean agent piping run overhead, hang from the roof or floor framing alongside trays and busway. They belong in the hung-load allowance.
- Clean agent storage. Cylinders for clean agent systems are heavy and are usually grouped in a dedicated room or rack near the protected space. That is a concentrated floor load, and the room may need its own rating.
- Enclosure integrity. Total flooding systems hold their concentration only if the room is tight, so penetrations in walls and roof decks around protected rooms must be sealed. Discharge can also pressurize the room, which the walls and their framing must tolerate; the system designer sets those requirements.
- Fire separation. NFPA 75's separation of IT rooms, and the separation of battery and generator rooms required by codes, means rated walls framed into the steel structure. The handbook notes that typical assemblies are 1 or 2 hours, while TIA can call for bearing walls rated up to 4 hours for the highest tier. See our fire-rated assemblies and US fire-resistance requirements.
Containment changes the fire picture
The handbook gives a specific warning about hot and cold aisle containment. It is good for energy, but it can:
- obstruct sprinkler spray patterns at the ceiling;
- delay a total flooding agent from reaching the fire if the agent is released in a different aisle;
- dilute smoke with high airflow, so detectors respond later.
Containment panels and doors are often hung from the structure, so their layout, the sprinkler layout and the steel above must be coordinated together. Our PUE and the building shell article explains why containment is now standard.
Protecting the steel itself
Where codes or standards require fire-resistance-rated structural members, the rating comes from tested assemblies using board, sprayed fire-resistive material or intumescent coatings. The choice affects appearance, durability, schedule and cost. Shop-applied intumescent can save site time; sprayed cementitious fireproofing is economical for concealed members. See intumescent vs SFRM and cementitious fireproofing. A later article in this series covers fire-resistance-rated steel for data centers in detail.
Where World Steel fits
World Steel designs and fabricates the steel for data centers with fire protection coordination in mind: clear heights that allow sprinkler clearance over cabinets, hung-load capacity for sprinkler and agent piping, framing for rated walls and agent storage rooms, and members prepared for the fireproofing system the design specifies, including shop-applied intumescent where chosen. Coatings are applied in our own plant in Vietnam by painters trained and certified by the paint manufacturer, with inspection accredited under IAS AC472. Our customers are US contractors; site work, including erection, is their scope, and their Engineer of Record approves and seals the design. Fire protection system design is by the project's fire protection engineer. See the data center building package for the full shell scope.
Key takeaways
- NFPA 75 applies where adopted; it requires IT room separation, sprinklers where the building needs them, and automatic detection.
- Tier III and IV facilities may need both sprinklers and clean agent; insurers may add their own standards.
- Corrosive smoke makes early detection valuable, and containment can delay both suppression and detection.
- Sprinkler clearance, piping loads, agent storage, rated walls and member fireproofing are all structural coordination items.
Source: H. Geng (ed.), Data Center Handbook, 2nd ed., Wiley, 2021, Chapters 12 and 28; NFPA 75. Ideas are paraphrased; the adopted codes and the current NFPA standards govern.
Quick answers
Is NFPA 75 mandatory?
Not by default. The Data Center Handbook notes that NFPA 75 is not referenced by the IBC or NFPA 101 and is referenced by the NEC only as a non-required standard, so it applies when an authority, insurer or owner adopts it.
What does NFPA 75 require?
Among other things, fire separation of IT rooms, sprinkler protection where the building requires sprinklers, and automatic detection.
Do top-tier data centers use both sprinklers and clean agent?
Often. The handbook notes that Tier III and IV facilities may require both, while lower tiers typically meet minimum code requirements without clean agent systems.
How does containment affect fire protection?
Hot and cold aisle containment can block sprinkler spray patterns, delay a clean agent from reaching the fire if it is released in another aisle, and dilute smoke so detectors respond later.
Keep building your steel plan
Go further on USPEB.com
On this topic
Across the US market
- US codes and standardsIBC, AISC, AWS and MBMA, designed to
- Seismic steel structuresSDC D to F framing for West Coast jobs
- Crane building designUS crane standards for mill and bay buildings
- Design ReportWhat our US-code design report contains
- Large projects, 2,500 t a monthCapacity for large US general contractors
- Contractor partnershipLong-term supply for US contractors


