Four load sources
What the roof steel has to carry
Equipment weight
Operating weights of cooling units and fans, with their curbs, rails and isolation bases, from the equipment schedule.
Wind on equipment and screens
ASCE 7-22 rooftop structure and equipment provisions apply to the units and to screen walls, which can carry more wind than the unit behind them.
Snow drift
Screens and large units cause drifts on the roof around them, designed to ASCE 7-22 Chapter 7 for the ground snow at your site.
Seismic forces on equipment
In seismic regions the supports carry the ASCE 7-22 Chapter 13 forces on nonstructural components, with the anchorage your EOR specifies.
Dunnage done once
Dunnage that matches the equipment you actually buy
Rooftop dunnage is often drawn late, after the equipment is selected, and then field-welded to fit. We prefer to set it out from the equipment schedule as soon as the units are chosen, model it with the frame in Tekla and fabricate it with the roof steel, so the supports arrive cut, drilled and marked for the unit they carry.
If the equipment changes, the model shows which supports move. Dunnage is bolted where possible so a unit can be replaced in future without cutting the roof frame.
Below the roof
Hung services and how the frame takes them
| Service | Typical support | What we coordinate |
|---|---|---|
| Cable tray and ladder rack | Threaded-rod hangers or strut from purlins and secondary steel | Hanger module and allowance per run from your electrical model |
| Busway | Hanger steel at fixed centers | Deflection limits from the busway maker, agreed with your EOR |
| Ducts and air handling | Trapeze supports and framed openings | Openings, headers and duct weights from your mechanical model |
| Sprinkler and pre-action mains | Hangers to the roof structure | Pipe weights and hanger points from your fire protection engineer |
How we coordinate it
From an equipment schedule to steel on the roof
-
Equipment schedule in
Weights, footprints, curb types and isolation from your MEP engineers.
-
Loads agreed
Operating, wind, snow and seismic cases confirmed with your Engineer of Record.
-
Modeled with the frame
Dunnage, screens, walkways and hanger steel in one Tekla model, checked against your MEP model.
-
Marked for the unit
Each support piece-marked for the equipment it carries and packed with its roof area.