ANSI/TIA-942, the Telecommunications Infrastructure Standard for Data Centers, is usually discussed by network designers. Chapter 12 of the Data Center Handbook edited by Hwaiyu Geng (2nd edition, Wiley, 2021), written by Alexander Jew, explains why builders should read it too. The standard defines the spaces a data center needs, the pathways that connect them, and a rating system that covers the architectural side of the facility as well as the electrical, mechanical and telecommunications systems. A TIA-942 data center rating is only as good as its weakest category, and the building is one of the categories. This article explains the system and what it asks of the structure.
Four categories, four levels
The handbook describes the TIA-942 rating as four separate scores:
- T for telecommunications;
- E for electrical;
- A for architectural, which covers the site, building construction and structure;
- M for mechanical.
Each is rated from 1, the lowest availability, to 4, the highest. Higher ratings include all the requirements of the lower ones and cost more. A facility is written as, for example, T3E2A4M3. The overall rating is the lowest of the four, so that facility is Rated 2 overall, because its electrical infrastructure is rated 2.
That rule matters for the building. An owner who invests in Rated 4 power and cooling but accepts a Rated 2 building gets a Rated 2 facility. The structure, envelope and fire separation must keep pace with the systems they house.
What each level means
The handbook's chapter on corrosion and contamination includes an appendix that summarizes the rated levels and their target availability:
| Rated level | Description, as summarized in the handbook | Availability |
|---|---|---|
| Rated 1 | Single, non-redundant distribution path; non-redundant capacity components | 99.671% |
| Rated 2 | Rated 1 plus redundant capacity components | 99.741% |
| Rated 3 | Multiple independent distribution paths; dual-powered IT equipment; concurrently maintainable | 99.982% |
| Rated 4 | Fault tolerant; cooling equipment independently dual-powered; power storage and distribution designed for fault tolerance | 99.995% |
The handbook describes Rated 1 as essentially a server room following basic installation guidelines, and Rated 4 as a facility for mission-critical systems with fully redundant subsystems and compartmentalized security zones. Our companion article on tiers and redundancy explains the N, N+1 and 2N language behind these levels.
The computer room as a structural brief
Chapter 12 also summarizes TIA guidance for the computer room itself. Several items are structural requirements in disguise:
| Item | Guidance summarized in the handbook |
|---|---|
| Ceiling height | At least 2.6 m (8.5 ft) for cabinets up to 2.13 m (7 ft); more for taller cabinets |
| Sprinkler clearance | At least 460 mm (18 in) between cabinet tops and sprinklers |
| Floor capacity | At least 7.2 kPa (150 lb/ft²); 12 kPa (250 lb/ft²) recommended |
| Ceiling hanging capacity | At least 1.2 kPa (25 lb/ft²); 2.4 kPa (50 lb/ft²) recommended |
| Location | Away from elevators, exterior walls, the building core and immovable walls that block expansion |
| Openings | No windows or skylights |
For a steel building, the hanging capacity is the most important line. Cable trays, busway, containment, lighting and fire protection all hang from the roof or floor framing above. A frame designed for the recommended 2.4 kPa (50 lb/ft²) hung load, rather than the minimum, gives the facility room to grow through several IT refresh cycles. Our data hall frames guide and cable tray supports explain how the hung loads reach the frame.
The location rule also has a structural reading. A computer room that sits away from the building core and exterior walls, with no windows, is easiest to achieve in a clear-span or long-span steel hall where the interior is free of fixed elements.
Redundant paths need physical separation
At higher ratings, TIA-942 asks for redundancy in the telecommunications infrastructure, and the handbook explains what that means physically. A Rated 2 cabling system needs redundant carrier routes into the building, going to different carrier central offices and separated by at least 20 m (66 ft) along their whole length. A Rated 3 system adds redundant telecommunications entrance rooms and two different carriers. A Rated 4 system adds redundant main, intermediate and horizontal distribution areas, with cabinets cabled to two different areas.
Each of those duplicated rooms and pathways takes space, and often structure: separate entrance points in the wall, separate duct banks, separate tray routes with their own supports. Planning the frame and wall openings for two entrance rooms at opposite sides of the building is far easier at the design stage than as a later change.
Fire separation at the top ratings
Chapter 28 of the handbook, on fire protection, adds one more structural item. Model building codes typically call for 1 or 2 hour fire-resistance-rated assemblies. The handbook notes that some standards, including TIA, can require bearing walls rated as high as 4 hours for the highest-rated facilities. Fire-resistance ratings on steel members come from tested assemblies, using board, sprayed fireproofing or intumescent coatings, so the rating target must be known when the steel is designed. See our fire-rated assemblies and the fire protection group.
Ratings are not the only scheme
The handbook notes that TIA-942 is one of several ways to assess reliability, alongside the Uptime Institute tier system, BICSI 002 classes and national standards such as China's GB 50174 and the Japan Data Center Council's outline, which even ties seismic design and probable maximum loss to its tiers. Whatever the scheme, the principle for the structure is the same: the building must support the rating of the systems it contains, and must never be the lowest score. Our article on Risk Category IV design covers the natural hazard side of that principle.
Where World Steel fits
World Steel designs and fabricates steel for data centers to the loads that follow from the owner's chosen rating: floor and hung-load capacities, clear heights, framed openings for redundant entrance rooms, supports for duplicated pathways, and members ready for the fire-resistance rating the design requires. Fabrication takes place in our own plant in Vietnam, with inspection accredited under IAS AC472. We design to the codes and standards the project specifies; rating assessment is carried out by the owner's chosen assessor. Our customers are US contractors; site work, including erection, is their scope, and their Engineer of Record approves and seals the design. See the data center building package for the full shell scope.
Key takeaways
- TIA-942 rates telecommunications, electrical, architectural and mechanical infrastructure from 1 to 4; the lowest category sets the overall rating.
- The handbook lists target availability from about 99.671% at Rated 1 to 99.995% at Rated 4.
- Computer room guidance sets floor capacity, ceiling hanging capacity, clear height and location, all structural decisions.
- Higher ratings bring duplicated entrance rooms and pathways, and fire-rated assemblies that can reach 4 hours.
Source: H. Geng (ed.), Data Center Handbook, 2nd ed., Wiley, 2021, Chapters 12, 15 and 28; ANSI/TIA-942-B. Ideas are paraphrased; the current edition of the standard governs.
Quick answers
What does a TIA-942 rating cover?
Four categories: telecommunications (T), electrical (E), architectural (A) and mechanical (M), each rated 1 to 4. The architectural category includes the site, the building and its structure.
How is the overall rating decided?
By the lowest category. A facility rated T3, E2, A4, M3 is a Rated 2 facility overall, because electrical is rated 2.
What availability do the rated levels correspond to?
The handbook lists about 99.671% for Rated 1, 99.741% for Rated 2, 99.982% for Rated 3 and 99.995% for Rated 4.
What does TIA say about computer room floors and ceilings?
As summarized in the handbook: floors of at least 7.2 kPa (150 lb/ft²) with 12 kPa (250 lb/ft²) recommended, ceiling hanging capacity of at least 1.2 kPa (25 lb/ft²) with 2.4 kPa (50 lb/ft²) recommended, and a ceiling height of at least 2.6 m (8.5 ft).
Keep building your steel plan
Go further on USPEB.com
On this topic
Across the US market
- Seismic steel structuresSDC D to F framing for West Coast jobs
- Crane building designUS crane standards for mill and bay buildings
- Design ReportWhat our US-code design report contains
- Large projects, 2,500 t a monthCapacity for large US general contractors
- Contractor partnershipLong-term supply for US contractors
- Solutions by stateState-by-state steel solutions