Building codes are written for typical buildings. A steel mill is not typical. Beside an electric arc furnace, the steel faces radiant heat and splashes of slag. Under a pickling line, it breathes acid fumes. In a scrap bay, it gets hit by magnets and loaders. At a quench or a cooling bed, it sits in hot steam. AIST Technical Report No. 13 (2021) recognizes this in Section 3.14, Extreme Environments, and in related rules on expansion joints, secondary framing, minimum thickness and maintenance access. This article pulls those rules together and explains how they shape the steel and its protection.
What Section 3.14 asks
Section 3.14 asks designers to consider, on top of the loads elsewhere in the report, the effects of extreme conditions in specific parts of the mill. Its examples are:
- extreme heat or cold;
- large impact forces;
- significant vibration;
- large mobile equipment loads;
- highly corrosive environments.
It asks that protective coatings for highly corrosive areas be discussed between the owner, the contractor and a coating supplier, and that the designer work with the owner to find which areas of the mill could be affected. The commentary is frank: heavy industrial facilities present extreme events and conditions that can be unpredictable and are not covered by any code, so identifying them area by area and planning for them is essential.
In practice, the most useful output is an environment map of the plant: a plan that marks each zone with its conditions, such as radiant heat near furnaces, corrosive fumes, high humidity, impact risk and washdown, and states the protection each zone needs.
Heat: temperature, expansion and strength
Heat affects steel in three ways.
Strength. Structural steel loses strength and stiffness at high temperature. For the long-term temperatures found near most mill processes this is small, but members close to a furnace roof, a ladle station or a slag pot area can run hot enough to matter, and they may need heat shields, cooling or a reduced design strength.
Expansion. Steel grows about 12 mm per 10 m for a 100 °C rise. TR-13 Section 5.6 recognizes that internal temperature swings in furnace buildings and other hot metal areas can be large, and recommends tighter spacing of transverse expansion joints there:
| Area | Recommended maximum spacing of transverse expansion joints |
|---|---|
| Furnace buildings and hot metal areas | About 122 m (400 ft) |
| Other mill areas | About 152 m (500 ft) |
| Width | Longitudinal joints when wider than about 152 m (500 ft) or more than five aisles |
Our article on bracing and expansion joints covers how the joints and bracing work together.
Secondary members. Section 5.11 asks that girts and purlins be designed for exposure to excessive heat where it applies. Thin cold-formed members near a hot process can distort, and their coatings can fail early.
Heat also affects coatings. Most standard paint systems are rated for limited service temperatures, so steel near hot processes may need heat-resistant coatings, such as silicone-based or inorganic zinc systems, chosen with the coating supplier for the actual temperature.
Cold
Extreme cold matters in unheated buildings and outdoor structures in northern states. The main structural concern is toughness: steel and welds become more brittle at low temperatures, so members under tension and repeated load, such as crane girders, may need steel and filler metal with specified Charpy V-notch toughness. Vietnam plate mills can supply EN 10204 3.1 certificates with Charpy results on request, which lets the material be tied to the toughness requirement by heat number.
Impact
Section 3.14 lists large impact forces as an extreme condition, and Section 5.11 adds vehicle impact and falling ice as loads for secondary framing. In a mill, impact comes from:
- loaders and forklifts striking columns and wall framing;
- magnet cranes swinging scrap against the structure;
- material falling from conveyors or charging buckets.
The commentary to Section 5.11 suggests a simple and effective answer: avoid the exposure. For vehicle impact on walls, the lower part of the wall can be concrete or masonry (a wainscot) instead of cladding on girts. For columns, bollards, concrete encasement or steel guards keep vehicles away. Where impact cannot be avoided, the member is designed for it.
Corrosion: fumes, water and dust
Mills have some of the most corrosive indoor environments in industry: acid fumes at pickling lines, chlorides and sulfur compounds from scrap and fuels, constant humidity at cooling and quench areas, and wet dust that holds moisture against the steel. TR-13 addresses corrosion in several places:
- Section 3.14: coatings for highly corrosive areas are agreed with the owner, the contractor and a coating supplier.
- Section 5.11: corrosion is considered in the design of girts and purlins.
- Section 5.12: metal exposed to marked corrosive action is protected as the owner specifies.
- Section 1.6.1: the design should not prevent parts of the structure from being cleaned and painted.
The commentary to Section 5.11 adds a practical point about galvanizing. Secondary members in severe environments can be protected with a heavier zinc coating and a specified minimum thickness, but the minimum thickness usually refers to the uncoated base metal, not the coated product. Cold-formed members are usually rolled from pre-galvanized sheet, while hot-rolled members and joists are hot-dip galvanized after fabrication, which gives a thicker coating.
Minimum thickness
Section 5.12 sets minimum material thicknesses for everything except secondary members such as purlins and girts:
| Location | Minimum thickness |
|---|---|
| Exterior construction | About 8 mm (5/16 in) |
| Interior construction | About 6 mm (1/4 in) |
For rolled shapes, the controlling thickness is the mean flange thickness, whatever the web thickness. These minimums give a margin against corrosion loss and handling damage that thin plates do not have. Our article on connections and minimum thickness covers the rest of Section 5.12 to 5.14.
Choosing the coating system
The coating system follows the environment map. A typical mill uses several systems:
- interior dry areas: a zinc-rich or epoxy primer with an epoxy or polyurethane finish;
- humid and wet areas: thicker epoxy systems, or hot-dip galvanizing with a paint topcoat (a duplex system);
- chemical fume areas: chemical-resistant epoxy or novolac systems chosen with the coating supplier;
- hot areas: heat-resistant systems rated for the service temperature.
ISO 12944 gives a framework for corrosivity categories and durability, and our articles on C5 very high corrosivity and CX extreme corrosivity explain the most severe categories in detail. Surface preparation, film thickness and inspection matter as much as the product.
Fire and molten metal
Heat in a mill is not only steady radiant heat. Molten metal spills, ladle breakouts and hydraulic oil fires are rare but real events, and the areas where they can happen are usually known: under ladle paths, around the furnace and the caster, and near hydraulic power units. TR-13 leaves the response to the owner and designer, in keeping with its call to plan for extreme events area by area. Typical measures include spill pits and curbs that keep molten metal away from column bases, heat shields on columns and girders along ladle routes, and fire protection on critical members where the owner or the code asks for it. Our structural steel fire protection solution covers the coatings and boards used for that purpose.
Putting the environment map to work
The environment map is useful only if it reaches the drawings. A simple way is to give each zone a code and show it on the general arrangement plans, then refer to it in the coating specification, the member schedule and the shop drawings. Each member then carries its zone code into the shop, where the paint shop applies the right system, and onto site, where the US contractor's crews know which touch-up product to use. The same map later guides the plant's maintenance painting program, because it shows where the coating will break down first and where inspections should start.
Access for maintenance
No coating lasts forever in a mill, so maintenance is part of the design. Section 1.6.1 asks that the design not prevent cleaning and painting, and that walkways, platforms and stairs give access for maintenance. Our article on crane maintenance access covers those provisions. Details matter too: closed box sections sealed against moisture, drainage holes where water could collect, and gaps between members wide enough to paint.
How World Steel applies it
World Steel designs, fabricates and coats steel structures for US projects. On a mill building, we:
- build the environment map with the owner and the US contractor, and assign a coating system to each zone;
- apply coatings in our own paint shop from major brands such as Jotun, PPG, Carboline, Hempel, Nippon and International Paint, including epoxy coatings and zinc-rich primers, so touch-up products are available in the US;
- use coatings that carry UL certification where specified, applied by painters trained and certified by the paint manufacturer, and inspected by our FROSIO Level III and BGAS coating inspectors;
- arrange hot-dip galvanizing with a project-specified galvanizer where the environment calls for it;
- design to TR-13's minimum thicknesses and expansion joint spacing.
The US Engineer of Record reviews and seals the design. Our plant is accredited under IAS AC472 and audited twice a year. Our coastal corrosion protection and lifecycle maintenance pages explain the coating and maintenance approach in more depth. Site touch-up and repair is the US contractor's scope.
Solutions and the Sunpro Steel project
Our heavy industrial plants solution shows how World Steel handles a full mill or heavy plant, and the crane building system page shows the runway package. For a factory with bridge cranes, start from manufacturing plants with crane bays. The Sunpro Steel mill project, about 5,000 t with 150 t cranes and a furnace area, is where these TR-13 points were applied at full scale.
Source and limits
This article paraphrases AIST Technical Report No. 13 (2021), Sections 1.6.1, 3.14, 5.6, 5.11 and 5.12 and the commentary to Sections 3.14 and 5.11. The thermal expansion figure is a general property of carbon steel. Coating systems are agreed with the owner, the contractor and the coating supplier on each project.
Quick answers
What minimum steel thickness does AIST TR-13 recommend?
About 8 mm (5/16 in) for exterior construction and 6 mm (1/4 in) for interior construction, excluding purlins and girts. For rolled shapes, the mean flange thickness is the controlling thickness.
How far apart should expansion joints be in a furnace building?
AIST TR-13 recommends transverse joints no more than about 122 m (400 ft) apart in furnace and hot metal buildings, and about 152 m (500 ft) elsewhere in the mill.
Who chooses the coating for corrosive mill areas?
AIST TR-13 asks the owner, the contractor and a coating supplier to agree it. World Steel applies systems from major brands such as Jotun, PPG, Carboline and Hempel in its own paint shop.
Keep building your steel plan
Go further on USPEB.com
On this topic
Across the US market
- Steel fire protectionIntumescent and fire-rated steel packages
- Quality hubCoating inspection by FROSIO Level III inspectors
- Products catalogGalvanized, painted and built-up members
- Download centerSample ITP, design report and approval drawings
- Large projects, 2,500 t a monthCapacity for large US general contractors
- Contractor partnershipLong-term supply for US contractors