A beam in a seismic frame does its job by forming a plastic hinge: a short length that yields and rotates while the rest of the beam stays elastic. Two things can spoil that hinge. The first is instability: if the beam is free to twist and buckle sideways, it will lose strength long before it reaches the rotation the design counts on. The second is a discontinuity: a weld, a hole or a nick in the yielding region that becomes the start of a crack. AISC 341-22 deals with both in Chapter D, with beam stability bracing in Section D1.2 and protected zones in Section D1.3. This article explains both, and why they are designed together.
Why yielding beams need more bracing
Ordinary beams are braced so they reach their design moment without lateral-torsional buckling. A seismic beam must do much more: it must reach its plastic moment, push into strain hardening and then rotate through many reversing cycles. As the compression flange yields, its stiffness drops sharply, and a flange that was stable when elastic becomes prone to sideways buckling. The bracing must hold it in place throughout.
That is why the bracing rules for seismic beams are stricter than those of AISC 360, and why they get stricter still for beams expected to undergo large rotations.
Section D1.2: spacing of beam bracing
AISC 341 sets the maximum unbraced length, Lb, according to the member's ductility class from Section D1.1:
- Moderately ductile beams: Lb ≤ 0.19 ry E/(Ry Fy).
- Highly ductile beams: Lb ≤ 0.095 ry E/(Ry Fy).
Here ry is the radius of gyration about the beam's weak axis, E the modulus of elasticity and Ry Fy the expected yield stress.
A worked example
Take an ASTM A992 beam with Ry Fy of about 380 MPa (55 ksi) and ry of 50 mm (about 2 in.). The highly ductile limit gives Lb ≤ 0.095 × 50 × 200,000/380 ≈ 2,500 mm, or about 2.5 m (8 ft). A special moment frame beam spanning 9 m (30 ft) therefore needs bracing at roughly three intermediate points along its length, in addition to the bracing at its hinges. The same beam as a moderately ductile member could be braced at about twice that spacing.
Which flange, and how
The bracing must restrain both flanges against lateral movement, or restrain the section against twisting. It can take two forms:
- Lateral bracing of both the top and bottom flanges, for example by the floor slab at the top and short kicker angles or struts at the bottom.
- Torsional bracing, such as a stiff beam or member framing perpendicular into the seismic beam with a connection that resists twisting.
A composite concrete slab on metal deck provides continuous bracing to the top flange. The bottom flange, which goes into compression when the beam bends the other way, still needs restraint where the standard asks for it. AISC 358 allows some prequalified connections, such as the reduced beam section with a composite slab, to omit supplemental bracing at the hinge under stated conditions. The connection's own rules decide.
Bracing at plastic hinges
At the location of an expected plastic hinge, Section D1.2 adds a requirement for special bracing close to the hinge, typically within a distance set by the system or the prequalified connection. Because the hinge region yields, the brace itself cannot be attached in the middle of it; it is placed just outside the protected zone.
The required strength of those braces is based on the beam's expected flexural strength, not on the design moment. In simplified form, a lateral brace adjacent to a plastic hinge is designed for a small percentage of the expected flange force, derived from Ry Fy Z divided by the distance between flange centroids, and its stiffness must meet the AISC 360 Appendix 6 requirements using that same expected moment. The result is a brace that holds the flange in place even as it yields and hardens.
Section D1.3: protected zones
A protected zone is the region of a member where large inelastic strains are expected. In those regions, even small flaws can trigger fracture, so AISC 341 bans the things that create them.
What is banned
Within a protected zone:
- Discontinuities created by fabrication or erection operations, such as tack welds, erection aids, air-arc gouging and thermal cuts, must be repaired as the Engineer of Record requires.
- Welded shear studs and decking attachments that penetrate the beam flange are not permitted, with limited exceptions. Arc spot welds that attach metal deck are permitted.
- Welded, bolted, screwed or shot-in attachments for perimeter edge angles, facades, partitions, ductwork, piping and other construction are not permitted.
- Holes for bolts, other than those part of the designed connection, are not allowed.
Outside the protected zone, attachments follow normal practice. The goal is a yielding region that is as smooth and uniform as the steel in the test specimen it was designed from.
Where protected zones are
Each system chapter defines its own protected zones. Some typical examples:
| System | Protected zone |
|---|---|
| Special moment frame | The beam region at each end subject to inelastic straining, for example from the column face to the end of a reduced beam section, as set by the connection |
| Intermediate moment frame | Similar to SMF, at the beam ends |
| Special concentrically braced frame | The middle portion of each brace and the zones next to each brace connection, plus elements that yield, such as gusset hinge zones |
| Eccentrically braced frame | The links |
| Buckling-restrained braced frame | The steel core and the elements that connect to it, as the standard defines |
| Steel plate shear wall | The web plates and the yielding regions of the boundary beams |
The Engineer of Record shows the exact locations and dimensions on the drawings, as required by Section A4.
Columns need bracing too
Beams are not the only members that must stay stable. In moment frames, AISC 341 also addresses the stability bracing of beam-to-column connections, where the column flanges must be restrained at the levels of the beam flanges so the joint does not twist out of plane as the beams yield. Where the column is expected to remain elastic, bracing at the level of the top flanges of the beams, often provided by the floor slab, may be enough. Where the column could yield, or where no slab is present, both flange levels are braced. Unbraced connections, such as those at a double-height space, are designed with the column treated as unbraced over the full height between lateral supports, with stricter strength checks. These rules belong to the system chapters, but they follow the same logic as Section D1.2: keep the yielding parts straight.
A practical layout sequence
On a real moment frame, the bracing and protected zones are best laid out in a fixed order:
- Mark the plastic hinge locations from the connection type and the analysis.
- Draw the protected zone around each hinge, with dimensions from the system chapter or the prequalified connection.
- Place the special braces adjacent to each hinge, just outside the protected zone, and size them for expected strength.
- Fill in the intermediate braces along the span to meet the Lb limit for the ductility class.
- Lay out studs, deck attachments, clips and hangers last, keeping them out of the protected zones.
- Check every column-to-beam joint for the bracing the system chapter requires.
Done in this order, the conflicts described below are resolved on paper.
Why bracing and protected zones are designed together
The two rules interact. The brace needed at a plastic hinge must be connected to the beam, but it cannot be connected inside the protected zone. Studs needed for composite action cannot be welded in the protected zone, which affects the slab's ability to brace the top flange there. Clip angles that support ceilings, ducts or facades must be moved out of the zone, which can conflict with the bracing location.
Good seismic detailing resolves these conflicts on the drawings, before steel is cut. Poor detailing leaves them to the site, where a well-meaning trade may weld a hanger right where the beam is meant to yield.
What fabricators and contractors should watch for
- Bracing connections located inside the protected zone on the shop drawings: a sign the detailing needs another look.
- Shear studs shown continuously along a moment frame beam: studs must stop at the protected zone, with only the permitted deck attachments inside it.
- Erection aids and lifting lugs near beam ends: they must be placed outside protected zones or removed and repaired as the engineer directs.
- Trades on site attaching to the steel after the erector leaves: marking the protected zones on the steel helps prevent damage.
How World Steel details bracing and protected zones
World Steel designs and fabricates seismic steel for US projects in its own IAS AC472-accredited plant in Vietnam. On every seismic frame our engineers check beam bracing spacing to Section D1.2 for the member's ductility class, design the braces adjacent to plastic hinges for expected strength, and place them, along with clips, studs and erection aids, outside the protected zones. The zones are drawn with dimensions on the shop drawings and erection drawings.
In the plant, tack welds and erection aids are kept out of protected zones, and every zone is checked for arc strikes, gouges and stray welds before coating; our protected zone fabrication article explains how. On request we mark protected zones on the steel so the US contractor's crews and the trades that follow can see them. Bracing members, bracing connections and stiffeners are fabricated with the frame, so the whole bracing system arrives on site ready for the US contractor to set, and the Engineer of Record approves the layout before fabrication.
The next article moves to connections: the seismic rules for bolted and welded joints in Section D2.
Quick answers
What is the bracing spacing limit for a highly ductile beam?
AISC 341 limits the unbraced length of highly ductile beams to about 0.095 ry E/(Ry Fy) and of moderately ductile beams to about 0.19 ry E/(Ry Fy), where ry is the radius of gyration about the weak axis.
Does a concrete slab count as beam bracing?
A composite slab braces the top flange. Bracing the bottom flange, or providing torsional bracing, is still needed where the standard requires it, unless a prequalified connection or test data shows it is not.
What is not allowed in a protected zone?
Welded, bolted, screwed or shot-in attachments for things like edge angles, facades, partitions, ducts and piping are not allowed, nor are holes and other discontinuities from fabrication or erection, except as the standard permits. Arc spot welds that attach metal deck are permitted.
Who shows the protected zones?
The Engineer of Record shows their locations and dimensions on the structural design drawings, and the shop and erection drawings repeat them. They can also be marked on the steel.
Keep building your steel plan
Go further on USPEB.com
On this topic
Across the US market
- US codes and standardsIBC, AISC, AWS and MBMA, designed to
- Seismic steel structuresSDC D to F framing for West Coast jobs
- Crane building designUS crane standards for mill and bay buildings
- Design ReportWhat our US-code design report contains
- Large projects, 2,500 t a monthCapacity for large US general contractors
- Contractor partnershipLong-term supply for US contractors