Cantilever column systems: OCCS and SCCS under AISC 341-22

In a cantilever column system, every column stands on its own, fixed at the base, and nothing else resists the earthquake. AISC 341-22 gives ordinary and special cantilever column systems full provisions for the first time, with new rules for column bases and column bracing.

· 7 min read · World Steel USA engineering team

Look at a fuel station canopy, a row of carport structures, a solar canopy over a parking lot or the open shed at a transit depot. Often there are no braces and no moment-resisting beams: just columns standing in the foundation and a roof on top. When the ground shakes, each column bends like a flagpole fixed at its base. That is a cantilever column system, and ASCE 7 lists it as a seismic force-resisting system in its own right. AISC 341-22 gives both versions, the ordinary cantilever column system (OCCS) in Section E5 and the special cantilever column system (SCCS) in Section E6, complete provisions and commentary, with new rules for column bases and column bracing. This article explains them.

How a cantilever column system works

In most steel frames, lateral load is shared by many members: beams and columns bending together in a moment frame, or braces in a braced frame. In a cantilever column system, there is no such sharing. Each column resists the lateral force tributary to it by bending, with the largest moment at the base. The roof or the beams on top tie the columns together so they move as a group, but they are not designed to resist moment at the column tops.

That simplicity has two consequences:

  1. No redundancy. If the base of a column fails, there is no alternative load path. Everything depends on the base and on the column's ability to bend.
  2. Large drift. A cantilever is flexible, and P-delta effects grow quickly as it sways, especially when the column carries significant gravity load.

ASCE 7 reflects both points by assigning low R factors and strict limits.

R factors and limits in ASCE 7

ASCE 7-22 Table 12.2-1 gives:

System R Ω0 Cd AISC 341 section
Special steel cantilever column system (SCCS) 2.5 1.25 2.5 E6
Ordinary steel cantilever column system (OCCS) 1.25 1.25 1.25 E5

With R = 1.25, an OCCS is designed for almost the full elastic force. An SCCS, at R = 2.5, is designed for half that, in exchange for ductile detailing.

ASCE 7 adds two important limits. The structural height of cantilever column systems is limited, about 10.7 m (35 ft) where they are permitted in higher Seismic Design Categories, and the use of OCCS is restricted in the higher categories. And Section 12.2.5.2 limits the required axial strength of each cantilever column, in the load combinations with seismic load, to a small fraction of its available axial strength. A column that carries a heavy axial load cannot yield safely in bending, so the system is meant for light roofs.

Ordinary cantilever column systems: Section E5

An OCCS is expected to provide minimal inelastic drift capacity through flexural yielding of the columns. Because it is designed for nearly elastic forces, its requirements are modest: columns designed for the seismic load combinations, with the base designed for the forces the column can deliver or the overstrength load, and connections and bases detailed so a brittle failure does not precede the column yielding. The 2022 edition clarifies the column base and bracing requirements for OCCS as well.

Special cantilever column systems: Section E6

An SCCS is expected to provide limited inelastic drift capacity through flexural yielding of the columns, usually near the base. To make that yielding ductile, AISC 341-22 requires:

  • Highly ductile columns, meeting the strict width-to-thickness limits of Table D1.1, so the column does not buckle locally at the plastic hinge.
  • A protected zone at the region of the column where the hinge is expected, normally just above the base, kept free of welds, holes and attachments.
  • Column bracing that meets new spacing and stiffness requirements, so the column does not buckle laterally or twist as it yields.
  • Column bases designed for the column's expected flexural strength and the corresponding shear, so the hinge forms in the column and not in the base plate, anchor rods or foundation.
  • Demand-critical welds at the column-to-base plate joint, where the full expected moment of the column passes into the base.

The column base: the heart of the system

The 2022 edition puts its strongest emphasis on column bases, and for good reason. In a cantilever column system the base must:

  1. Resist the column's plastic moment, increased for expected strength, without yielding or slipping first. That usually means a thick base plate, stiffeners, large anchor rods and a deep or wide footing.
  2. Transfer the shear that accompanies that moment, through shear lugs, embedment or anchor rods detailed for shear, not by friction alone.
  3. Stay stiff enough that base rotation does not add excessive drift. A base that rotates under load acts like a hinge, and a cantilever on a hinge has no lateral resistance at all.

The base design is shared between the steel designer and the foundation designer. Anchor rods and shear lugs are designed under ACI 318 Chapter 17, and the base plate and its welds under AISC 360, AISC 341 and AISC Design Guide 1. Embedded column bases, where the column is cast into the foundation, are an alternative that suits some sites.

Column bracing: new requirements

Cantilever columns are often slender and unbraced over their full height. AISC 341-22 sets spacing and stiffness requirements for the stability bracing of cantilever columns, so the column's compression flange cannot buckle out of plane as it yields near the base. Where the roof framing or a girt line braces the column, that bracing must meet the requirements; where no bracing is practical, the column section must be stocky enough to be stable over the full height.

Where cantilever column systems fit

The system suits light structures with a single level of mass at the top:

It is not a fit for heavy roofs, buildings with significant gravity load on the columns, tall structures or anything that needs redundancy.

A worked example: a solar carport row

Picture a solar carport over a parking lot in a Seismic Design Category D region: a row of single columns at 7.5 m (24 ft 7 in.) spacing, each carrying a cantilevered beam that supports purlins and a solar array. The roof is light, so the axial load in each column is small, and the cantilever column system is a natural fit along the row and across it.

As an SCCS, the design force is half the elastic force. The columns are wide-flange or HSS sections chosen to meet the highly ductile width-to-thickness limits, and they are checked for drift with Cd = 2.5 and P-delta effects. The column base is designed for the column's expected flexural strength: a stiffened base plate, four or more large anchor rods and a shear lug, sitting on a drilled pier or spread footing sized by the foundation engineer. The lower part of the column, where the hinge is expected, is a protected zone, so the conduit clamps and lighting brackets that every carport needs are attached higher up the column or to the beam.

As an OCCS, the column and base would be designed for nearly twice that force, with less detailing. For a light carport, the OCCS can still be economical where it is permitted; for taller or heavier canopies, the SCCS usually wins. Wind uplift and snow on the panels are checked alongside seismic, and in many regions wind governs.

Design tips

  • Check the axial load limit early. If a column carries heavy gravity load, for example from rooftop equipment or snow, the cantilever system may not be allowed.
  • Watch the drift. With Cd equal to R, drifts are roughly elastic, and P-delta can govern. Stiffer, deeper columns are often needed.
  • Design the base and foundation together. A cantilever column is only as good as its base. Coordinate anchor rods, plate thickness and footing size before the drawings go out.
  • Keep the protected zone clear. Clips for signage, lighting or electrical conduit near the column base are a common violation.
  • Think about wind. In many regions, wind governs canopy design; check both.

How World Steel designs and fabricates cantilever column systems

World Steel designs and fabricates canopies, carport structures and open steel structures for US projects in its own IAS AC472-accredited plant in Vietnam. On seismic sites we design to AISC 341-22 Section E5 or E6 as the Engineer of Record selects, check the ASCE 7 axial load limit and drift, size columns to the highly ductile limits for SCCS, and design the base plates, stiffeners and anchor rods for the column's expected strength. Base plates, stiffeners and the column-to-base welds are made by welders qualified to AWS D1.8, and the protected zone is shown on the shop drawings.

We supply anchor rods and setting templates with the steel so the US contractor can set them accurately in the foundation, and our engineers coordinate anchor layouts with the foundation designer before release. For large solar and EV canopy programs, our plant capacity of 2,500 t of steel a month and real-time tracking in PEB Studio keep repeat structures moving on schedule. The Engineer of Record reviews and approves the design.

The next article moves to Chapter F and the most common seismic system in steel: concentrically braced frames.

Quick answers

What is a cantilever column system?

A seismic system in which lateral resistance comes only from columns fixed at their bases and acting as vertical cantilevers, with no moment-resisting beam connections or bracing. Canopies, carports and some single-storey structures use it.

What R factor does a cantilever column system get?

ASCE 7-22 assigns R = 1.25 to ordinary steel cantilever column systems (OCCS) and R = 2.5 to special steel cantilever column systems (SCCS), so they are designed for high seismic forces.

Is there an axial load limit on cantilever columns?

Yes. ASCE 7 limits the required axial strength of each cantilever column, in the combinations with seismic load, to a small fraction of its available axial strength, so the column can yield in bending without crushing.

What changed for cantilever columns in AISC 341-22?

The 2022 edition gives both OCCS and SCCS complete provisions and commentary, with specific requirements for the shear and flexural strength of column bases and for the spacing and stiffness of column bracing.

Keep building your steel plan

Go further on USPEB.com

Keep going in the series

AISC 341-22 seismic design series

Twenty in-depth articles on the 2022 Seismic Provisions for Structural Steel Buildings: what each chapter asks of the design, the drawings, the shop and the inspector, and how World Steel engineers and fabricates seismic steel to it for US projects.

Chapter D
Members and connections

Ductile sections, bracing, protected zones, joints, splices and bases.

Chapter E
Moment frames

OMF, IMF, STMF, SMF and the cantilever column systems.

Chapter F
Braced frames and walls

Concentric and eccentric bracing, buckling-restrained braces, plate walls.

Chapters G–H
Composite systems

Steel and concrete working together, including the new CC-PSW/CF.

Chapters I–K
Fabrication, QA and testing

Shop and site rules, quality control and assurance, cyclic tests.